| 提交詢價信息 |
| 發(fā)布緊急求購 |
價格:電議
所在地:北京
型號:UC-KB-2008D
更新時間:2016-06-29
瀏覽次數:1643
公司地址:北京市通州區(qū)永順西街32號
![]()
周先生(先生) 經理
UC-KB-2008D型
氣體報警控制器
使用說明書
目 錄
1. 引言·····························································2
1.1 簡述·······················································2
1.2 技術指標···················································2
1.3 主要功能···················································2
2. 安裝····························································3
2.1 安裝尺寸···················································3
2.2 接線·······················································4
2.3 開通························································4
3. 操作說明························································5
3.1 面板說明···················································5
3. 2 工作狀態(tài)說明···············································6
4. 使用調整························································9
5. 報警處理························································9
6. 故障診斷與處理··················································10
7. 維護維修 ·······················································10
8. UC-KT-2021型氣體探測器說明書····································11
1.引言
本手冊分兩部分,分別詳細介紹了UC-KB-2008D型氣體報警控制器(見圖1)及UC-KT-2021型氣體探測器的安裝,操作及維護。在使用和安裝前請仔細閱讀本手冊。
1.1 簡述
UC-KB-2008D型氣體報警控制器(以下簡稱控制器),它與(4~20)mA標準信號氣體探測器(以下簡稱探測器)配合使用。探測器固定安裝在可能有氣體泄露的室內、外危險場所。控制器接受探測器傳來的電信號,并對之進行濾波、模數轉換、線性化、濃度計算等一系列處理工作,得到當前所測氣體的濃度值。當濃度值達到預先設定的報警值時,控制器即可發(fā)出聲、光報警及控制信號,提示操作人員采取安全對策或自動啟動相關設備,從而避免發(fā)生爆炸事故。控制器具有比較完善的自診斷功能,可對系統(tǒng)的各種故障進行處理,以便及時維修。
控制器設計符合國標GB16808-1997《可燃氣體報警控制器技術要求和試驗方法》,經過公安部消防產品合格評定中心評定,獲得產品型式認可證書,編號:ROS。經過北京市相關質量技術監(jiān)督部門的考核,獲得制造計量器具許可證,證號:京[制]01120010號。
1.2 技術指標
供電電壓:交流(187~242)V
線性誤差限:±5% F.S
功 耗: <50W [與通道容量有關]
工作溫度:(0~40)℃
工作濕度:≤95%
通道容量:[本機為12點]
報警設置:高、低限報警兩級報警
觸點輸出:高、低限報警各有1組無源常開觸點(電容量220VAC 2A)
傳輸距離:≤1km(線阻小于20Ω)
箱體規(guī)格:[見圖1]
重 量:[與通道容量有關]
1.3 主要功能
1.高、低限報警各對應相應的聯(lián)動輸出。
2. 控制器具有自檢功能,可對機器的重要部件和面板上所有指示燈進行檢查。
3. 帶有散熱裝置。
4.當有下列情形之一時,控制器能在30s內發(fā)出與報警信號有明顯區(qū)別的聲、光故障信號:
a. 探測器與控制器連接線斷路。
b. 探測器內部元件失效。
c. 控制器主要元件失效。
2 安裝
2.1 安裝尺寸(如圖1)
圖1 控制器外觀尺寸 圖2 控制器接線說明
2.2接線
控制器的后端蓋,可見如圖2 、圖3的接線端子板、電源插座。
A. 插座所帶電源線連接到外部電源,將內部電源線插于插座上。并查看插座開關是否開啟。
B.直流電源線 [V+、V-]:V+、V-為24V直流電輸出端。
C.信號線:信號線采用3芯儀表用控制電纜,與探測器相連,線徑及傳輸距離見表1。將控制器上的P,S,G分別與探測器的P,S,G相連。
表1 線徑及傳輸距離
|
電纜橫截面(mm) |
0.75 |
1.0 |
1.5 |
|
遠傳輸距離(M) |
500 |
750 |
1000 |
圖3控制器單個接線板示意圖
注意: 1、控制器與探測器連接時,注意控制器P,S,G與探測器P,S,G相對應,切勿接反!
2、安裝布線工程應符合GB 50093-2002《工業(yè)自動化儀表施工
3、驗收規(guī)范》或《中華人民共和國危險場所電氣安裝規(guī)范》。
D.通訊線:R+、R-,為RS-485信號線。
E.聯(lián)動輸出接線:高限報警的控制輸出端子為常開觸點HA、HB。低限報警的控制輸出接線端子為常開觸點LA、LB。輸出信號為無源觸點信號,聯(lián)動接線線徑應根據所連接設備的具體情況選定。
F. (4~20mA)標準信號輸出:I, 標準信號輸出端子(相對于直流電源負G)
注意:(4~20mA)標準信號輸出功能為可選配功能,定貨時必須注明。
2.3 開通
2.3.1 檢查安裝接線正確無誤后,開機。先開主電,再打開備電開關;系統(tǒng)進入預熱狀態(tài),預熱大約1分鐘后進入檢測狀態(tài)。
注:控制器在通電后上邊的散熱風扇自動開啟。
3、操作說明
3.1 面板說明
3.1.1 面板示意圖(見圖4)
圖4 操作面板示意圖
3.1.2 指示燈說明(見表2)
表2 指示燈說明
|
指示燈說明 |
顏色 |
功能 |
|
報警 |
紅 |
發(fā)生報警時,該指示燈亮;返回監(jiān)控態(tài)后,按復位鍵熄滅。 |
|
故障 |
黃 |
探測器存在故障時,該指示燈亮 |
|
電源 |
綠 |
控制器通電時,該指示燈亮 |
3.1.2 功能鍵說明(見表3)
表3 功能鍵說明
|
鍵名 |
功能 |
|
消聲|上下 |
當控制器發(fā)生報警或故障時,按下此鍵可以消除聲音報警/故障信號。上下鍵功能見具體功能說明。 |
|
復位|回車 |
按下此鍵,可使控制器所有報警/故障復位。回車鍵功能見具體功能說明。 |
|
自檢|左右 |
當控制器處于監(jiān)控狀態(tài)時,按下此鍵,即對控制器面板指示燈、顯示器、聲報警進行功能檢查。左右鍵功能見具體功能說明。 |
3.2 工作狀態(tài)說明
3.2.1 系統(tǒng)初始化狀態(tài)
控制器加電,控制器進入系統(tǒng)初始化,此時,濃度顯示”----”,時鐘顯示初始化進行時間。初始化狀態(tài)大約持續(xù)60秒后,系統(tǒng)進入監(jiān)控狀態(tài)。
3.2.2 監(jiān)控狀態(tài)
在監(jiān)控狀態(tài)下, 濃度顯示濃度值,無故障,無報警。
3.2.3 自檢態(tài)
在監(jiān)控狀態(tài)下,按自檢鍵,進入自檢狀態(tài)。此時,液晶、面板上所有的指示燈和LED都點亮,蜂鳴器響。
3.2.4 報警態(tài)
在監(jiān)控狀態(tài)下,如果氣體濃度超過報警濃度,控制器即進入報警態(tài)。此時報警指示燈亮,“%LEL”顯示相應濃度值,同時報警蜂鳴器響。功能號、報警級別顯示區(qū)顯示報警級別。報警后處理措施見<5.報警處理>。
報警級別:A1-低限報警(第1級報警)。
A2-高限報警(第2級報警)。
A3-第3級報警。
A4-第4級報警。
3.2.5 故障態(tài)
在監(jiān)控狀態(tài)下,若探測器發(fā)生故障,控制器即進入故障態(tài)。此時故障指示燈亮,故障蜂鳴器響。
故障診斷與處理見<6.故障診斷與處理>。
3.2.6 功能態(tài)
在監(jiān)控狀態(tài)下,按回車鍵進入功能態(tài),此時功能號顯示區(qū)閃爍,此時可以先按上下鍵再按回車鍵,切換到子功能號選擇、時鐘設置、故障記錄、報警記錄等狀態(tài),或者按左右鍵返回監(jiān)控狀態(tài)。
3.2.6.1 子功能號選擇
在本功能態(tài)下,功能號顯示焦點位閃爍,按左右鍵切換輸入焦點,上下鍵改變焦點位數值,按回車鍵進入子功能態(tài)(見下表4)。
表4 子功能態(tài)表
|
功能號 |
功能說明 |
|
1 |
儀表地址 |
|
2 |
通訊速率 |
|
3 |
通道屏蔽 |
|
4 |
探頭類型 |
|
5 |
單位 |
|
6 |
小數位數 |
|
7 |
濾波系數 |
|
8 |
報警模式 |
|
9 |
報警有效性 |
|
10 |
量程上限 |
|
11 |
量程下限 |
|
12 |
報警下限(第1報警點) |
|
13 |
報警上限(第2報警點) |
|
14 |
第3報警點 |
|
15 |
第4報警點 |
|
16 |
死區(qū) |
|
17 |
回差 |
|
18 |
顯示更改密碼 |
|
19 |
密碼有效性 |
|
20 |
年份設置 |
|
21 |
月日設置 |
|
22 |
高報脈動有效性設置 |
注:*-本功能無效
3.2.6.1.1 儀表地址
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:儀表地址在與上位機通訊時區(qū)分通道,有效范圍1~254。
3.2.6.1.2 通訊速率
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:儀表與上位機通訊采取”9600,n,8,1”模式,采用ModBus RTU協(xié)議。通訊波特率默認9600,另有4800, 2400可供選擇,分別由0、1、2代表9600、4800、2400三種波特率。
3.2.6.1.3 通訊屏蔽
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:1-通道屏蔽有效,通道響應探測器的濃度變化,但不報警;其它-無效
3.2.6.1.4 探頭類型
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。見附錄1。
3.2.6.1.5 單位
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。見附錄2。
3.2.6.1.6 小數位數
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:小數位數數值區(qū)間為0~3,默認值0。
3.2.6.1.7 濾波系數
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:濾波系數數值區(qū)間為1~50,默認值20。
3.2.6.1.8報警模式
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.9報警有效性
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.10 量程上限
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.11 量程下限
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.12 報警下限(第1報警點)
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.13 報警上限(第2報警點)
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.14第3報警點
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.15第2報警點
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.16死區(qū)
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.17回差
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
4.2.6.1.18 顯示更改密碼
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
3.2.6.1.19 密碼有效性
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)。
注:0-密碼無效;1-密碼有效,發(fā)生報警后,必須輸入密碼正確,才能復位。
3.2.6.1.20年份設置
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài),
注:本控制器的有效年份為2000~2099。
3.2.6.1.21月日設置
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)
注:濃度顯示區(qū)前兩位為月份,后兩位為日期。
3.2.6.1.22高報輸出設置
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)控態(tài)
注:濃度顯示區(qū)四位數字全為0,高報后長輸出,按復位取消;否則高報脈動輸出(閉合時間大約0.5s)。
3.2.6.2 時鐘設置
在本功能態(tài)下,按左右鍵進入輸入狀態(tài)和改變輸入焦點,上下鍵更改數值,按回車鍵確認,返回監(jiān)測態(tài)
3.2.6.3 故障記錄
3.3.6.4 報警記錄
4.使用調整
在檢查安裝接線準確無誤后,打開電源開關,控制器進入系統(tǒng)初始化狀態(tài),大約30秒后,進入監(jiān)控狀態(tài)。如果控制器存在故障,按《6故障診斷與處理》進行處理。如果存在通道漂移,按《4.1通道校正》進行調整。報警系統(tǒng)進入正常運行狀態(tài)。
4.1通道校正
若通道的漂移過大(超過5%F.S),則必須進行通道校正。校正時用電流校正表,在S(+)、G(-)之間輸入4mA電流,用一字型螺絲刀調整通道零點調整電位器SW0,使得AB點之間電壓差<1mV;,在S(+)、G(-)之間輸入16mA電流,當前濃度在75±1%LEL之間擺動即可。
5.報警處理
5.1 在監(jiān)控狀態(tài)下,當濃度達到低限報警濃度時,控制器進入報警狀態(tài)。當濃度達不到低限報警濃度時,按復位鍵,控制器返回監(jiān)控狀態(tài)。、
5.2在報警狀態(tài)下,按“消聲”鍵,清除報警蜂鳴聲,同時消聲指示燈亮,再按一次“消聲”鍵,消聲狀態(tài)清除,報警蜂鳴器響,消聲指示燈滅。
6.故障診斷與處理
6.1 在故障狀態(tài)下,故障指示燈亮。此時可以按“消音”鍵去除故障聲音信號。
6.2在故障狀態(tài)下, 顯示“--”說明有故障。可采取以下措施排除故障。
1. 檢查控制器與探測器的連線是否正常;
2.若連線無誤,用萬用表測量S、G間電壓在0.2~1V之間.若有異常則表示探測器故障;若無異常,請通知本公司進行處理。
6.3故障處理完后,可以按“復位”鍵返回監(jiān)控態(tài)。
7. 維護維修
7.1 日常維護
當系統(tǒng)安裝完成后,在正常使用過程中,應由專業(yè)人員每年對控制器按《4.1通道校正》
進行調整,防止發(fā)生漂移。
7.2 若控制器達到使用年限,應及時更換,否則容易造成零漂過大、誤報等問題,影響正常生產活動。
7.3 注意環(huán)境清潔,如防塵、防水,防油煙等。
地址:北京市通州區(qū)永順西街32號
郵編:101149
:
郵箱: 
主頁:
免責聲明:以上所展示的[UC-KB-2008D UC-KB-2008D氣體報警控制]信息由會員[北京創(chuàng)偉高科電子技術有限公司]自行提供,內容的真實性、準確性和合法性由發(fā)布會員負責。| 詢價標題 | |